Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this building. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this building or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
In Attendance: Customer and their agent | Type of building: Commercial and Residential | Temperature: Over 50 |
Weather: Light Rain | Ground/Soil surface condition: Wet | Rain in last 3 days: Yes |
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
1. |
The building inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks or abnormal condensation on building components. The building inspector shall: Describe the type of roof covering materials; and Report the methods used to observe the roofing. The building inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors. | ||||||
1.0 | ROOF COVERINGS Viewed roof covering from: Walked roof Roof Covering: Roll/Selvage Comments: | ||||||
Rolled asphalt roofing with tarred seams is in good condition. | |||||||
| |||||||
1.1 | ROOF FLASHINGS - Comments: | ||||||
| |||||||
| |||||||
| |||||||
1.2 | SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS Chimney (exterior): Masonry Comments: | ||||||
Chimney on right side is in use and has no rain cap. Rain caps protect brick from water damage. | |||||||
1.3 | ROOF DRAINAGE SYSTEMS - Comments: | ||||||
1.4 | ROOF STRUCTURE AND ATTIC (report leak signs or condensation) Roof-Type: Flat Roof Structure: Not visible Comments: | ||||||
1.5 | MASONRY CHIMNEY - Comments: | ||||||
Interior of both flues in masonry chimney | |||||||
| |||||||
1.6 | EXTERIOR ROOF ITEMS - Comments: | ||||||
| |||||||
| |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
2. |
The building inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The building inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components where deterioration is suspected. The building inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks. The building inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility. | ||||||
2.0 | WALL CLADDING FLASHING AND TRIM Siding Style: Brick Siding Material: Brick veneer Comments: | ||||||
2.1 | DOORS (Exterior) Exterior Entry Doors: Wood Comments: | ||||||
Rear exit door from restaurant has broken closure device. | |||||||
2.2 | WINDOWS - Comments: | ||||||
| |||||||
| |||||||
| |||||||
2.3 | FOUNDATION WALLS AND MORTAR JOINTS - Comments: | ||||||
2.4 | DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS Appurtenance: Sidewalk Comments: | ||||||
2.5 | VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) Driveway: Shared access Comments: | ||||||
2.6 | EAVES, SOFFITS AND FASCIAS - Comments: | ||||||
2.7 | POLARITY AND GROUNDING OF RECEPTACLES ON EXTERIOR WALLS OF INSPECTED STRUCTURE - Comments: | ||||||
2.8 | EXTERIOR CONDITION - Comments: | ||||||
| |||||||
| |||||||
| |||||||
2.9 | PARKING AREA - Comments: | ||||||
2.10 | FIRE ESCAPES - Comments: | ||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||
3. |
The building Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The building inspector shall describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The building inspector shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The building inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the building inspector or other persons. | ||||
3.0 | FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) Foundation: Brick Comments: | ||||
3.1 | WALLS (Structural) Wall Structure: Wood, Brick Comments: | ||||
3.2 | COLUMNS OR PIERS Columns or Piers: Supporting walls, Brick Walls Comments: | ||||
3.3 | FLOORS (Structural) Floor Structure: 2 X 8, Wood joists Comments: | ||||
3.4 | CEILINGS (structural) - Comments: | ||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
4. |
The building inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; and Sump pumps. The building inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heating equipment; and Location of main water supply shutoff device. The building inspector shall operate all plumbing fixtures, including their faucets and all exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The building inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functional drainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials. | ||||||
4.0 | PLUMBING DRAIN, WASTE AND VENT SYSTEMS Washer Drain Size: 1 1/2" Diameter (undersized) Plumbing Waste: Cast iron, ABS Comments: | ||||||
| |||||||
| |||||||
| |||||||
4.1 | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Water Source: Public Water Filters: None Plumbing Water Supply (into building): Copper Plumbing Water Distribution (inside building): Copper Comments: | ||||||
4.2 | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS Water Heater Power Source: Electric Comments: | ||||||
3 - GSW 184 L hot water tanks and one Giant 38.5 Gal hot water tank. Tanks are not identified as to destination of water. | |||||||
| |||||||
| |||||||
4.3 | MAIN WATER SHUT-OFF DEVICE (Describe location) - Comments: | ||||||
Main water shut off is located in hydro room in basement. | |||||||
| |||||||
4.4 | FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) - Comments: | ||||||
4.5 | MAIN FUEL SHUT OFF (Describe Location) - Comments: | ||||||
Main fuel supply is located in front sidewalk. There are individual meters with shut offs in front of hydro room. | |||||||
| |||||||
4.6 | SUMP PUMP - Comments: | ||||||
Sump pump does not come on automatically. When plugged in the pump emptied the pit but would not shut off. Float device is not working. | |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | |||
5(A). | ||||||
5.0.A | CEILING CEILING: DRYWALL WALLS: CERAMIC TILE FLOOR: CERAMIC TILE DOORS: HOLLOW WOOD Comments: | |||||
5.1.A | WALLS - Comments: | |||||
5.2.A | FLOOR - Comments: | |||||
5.3.A | DOORS - Comments: | |||||
5.4.A | SHUT OFFS FOR TAPS - Comments: | |||||
5.5.A | SINK CONDITION - Comments: | |||||
Mens vanity and sink | ||||||
| ||||||
5.6.A | TOILET SECURE - Comments: | |||||
Urinals | ||||||
| ||||||
5.7.A | EXHAUST FAN - Comments: | |||||
5.8.A | GFCI OUTLET - Comments: | |||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
5(B). | |||||||
5.0.B | CEILING CEILING: DRYWALL WALLS: CERAMIC TILE FLOOR: CERAMIC TILE DOORS: HOLLOW WOOD Comments: | ||||||
Ladies washroom | |||||||
| |||||||
5.1.B | WALLS - Comments: | ||||||
5.2.B | FLOOR - Comments: | ||||||
5.3.B | DOORS - Comments: | ||||||
Bathroom stall door has been damaged and repaired. | |||||||
| |||||||
5.4.B | SHUT OFFS FOR TAPS - Comments: | ||||||
Shut offs installed | |||||||
| |||||||
5.5.B | SINK CONDITION - Comments: | ||||||
Sinks and vanity | |||||||
| |||||||
5.6.B | TOILET SECURE - Comments: | ||||||
3 toilets | |||||||
| |||||||
| |||||||
5.7.B | EXHAUST FAN - Comments: | ||||||
5.8.B | GFCI OUTLET - Comments: | ||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | |||
5(C). | ||||||
5.0.C | CEILING CEILING: DRYWALL WALLS: DRYWALL & PANELING FLOOR: CONCRETE DOORS: HOLLOW WOOD Comments: | |||||
Staff mens room had no working light. Bulb maybe broken. | ||||||
| ||||||
5.1.C | WALLS - Comments: | |||||
Paneling rotted along floor beside toilet | ||||||
5.2.C | FLOOR - Comments: | |||||
5.3.C | DOORS - Comments: | |||||
Door frame split at lock area | ||||||
| ||||||
5.4.C | SHUT OFFS FOR TAPS - Comments: | |||||
5.5.C | SINK CONDITION - Comments: | |||||
Drain line attached and discharging into sink | ||||||
5.6.C | TOILET SECURE - Comments: | |||||
Water was shut off to toilet and tank lid missing. | ||||||
5.7.C | EXHAUST FAN - Comments: | |||||
5.8.C | GFCI OUTLET - Comments: | |||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | |||
5(D). | ||||||
5.0.D | CEILING CEILING: DRYWALL WALLS: PANELING FLOOR: CONCRETE DOORS: HOLLOW WOOD Comments: | |||||
Staff women's bathroom | ||||||
| ||||||
5.1.D | WALLS - Comments: | |||||
Panel on wall is rotted at bottom | ||||||
| ||||||
5.2.D | FLOOR - Comments: | |||||
5.3.D | DOORS - Comments: | |||||
Latch bolt on door | ||||||
5.4.D | SHUT OFFS FOR TAPS - Comments: | |||||
One tap for sink is not working. | ||||||
5.5.D | SINK CONDITION - Comments: | |||||
5.6.D | TOILET SECURE - Comments: | |||||
5.7.D | EXHAUST FAN - Comments: | |||||
5.8.D | GFCI OUTLET - Comments: | |||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
6(A). | |||||||
6.0.A | CEILING CEILING MATERIAL: DRYWALL WALLS: DRYWALL AND BRICK FLOORS: VINYL TILES WINDOWS: WOOD THERMAL SINGLE SASH Comments: | ||||||
Front bar and eating area | |||||||
| |||||||
6.1.A | WALLS - Comments: | ||||||
6.2.A | FLOORS - Comments: | ||||||
6.3.A | WINDOWS - Comments: | ||||||
Electric baseboard heaters under front windows tested and working. | |||||||
6.4.A | DOORS - Comments: | ||||||
6.5.A | OUTLETS AND WALL SWITCHES - Comments: | ||||||
6.6.A | SMOKE DETECTORS - Comments: | ||||||
6.7.A | SINKS - Comments: | ||||||
6.8.A | EXHAUST FAN - Comments: | ||||||
6.9.A | GFCI OUTLET - Comments: | ||||||
6.10.A | STAIRWELLS - Comments: | ||||||
There is no door at top of stairs from basement and bottom stair has latch to keep fire rated door open. | |||||||
| |||||||
6.11.A | ELECTRICAL DEFICIENCIES - Comments: | ||||||
Un-protected electrical cable on post at front entrance. | |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
6(B). | |||||||
6.0.B | CEILING CEILING MATERIAL: DRYWALL WALLS: DRYWALL AND BRICK FLOORS: LAMINATE DOORS: METAL EXTERIOR DOOR, WOOD DOOR WITH GLASS PANELS Comments: | ||||||
Rear bar area | |||||||
| |||||||
6.1.B | WALLS - Comments: | ||||||
6.2.B | FLOORS - Comments: | ||||||
6.3.B | WINDOWS - Comments: | ||||||
6.4.B | DOORS - Comments: | ||||||
| |||||||
| |||||||
6.5.B | OUTLETS AND WALL SWITCHES - Comments: | ||||||
6.6.B | SMOKE DETECTORS - Comments: | ||||||
6.7.B | SINKS - Comments: | ||||||
6.8.B | EXHAUST FAN - Comments: | ||||||
6.9.B | GFCI OUTLET - Comments: | ||||||
6.10.B | STAIRWELLS - Comments: | ||||||
Rear view of basement entrance. Door was padlocked and could not be accessed. | |||||||
| |||||||
6.11.B | ELECTRICAL DEFICIENCIES - Comments: | ||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
6(C). | |||||||
6.0.C | CEILING CEILING MATERIAL: DRYWALL WALLS: DRYWALL FLOORS: VINYL TILES DOORS: HOLLOW WOOD Comments: | ||||||
6.1.C | WALLS - Comments: | ||||||
ProTex ll chemical extinguisher for exhaust hood. Vent Pro exhaust hood was serviced in 2010. Hood exhaust tested and working at time of inspection. | |||||||
| |||||||
6.2.C | FLOORS - Comments: | ||||||
| |||||||
| |||||||
| |||||||
6.3.C | WINDOWS - Comments: | ||||||
6.4.C | DOORS - Comments: | ||||||
Compressor unit for cooler is located above kitchen entrance. | |||||||
| |||||||
6.5.C | OUTLETS AND WALL SWITCHES - Comments: | ||||||
6.6.C | SMOKE DETECTORS - Comments: | ||||||
6.7.C | SINKS - Comments: | ||||||
Sink and food prep area | |||||||
| |||||||
6.8.C | EXHAUST FAN - Comments: | ||||||
Exhaust fan | |||||||
| |||||||
6.9.C | GFCI OUTLET - Comments: | ||||||
6.10.C | STAIRWELLS - Comments: | ||||||
6.11.C | ELECTRICAL DEFICIENCIES - Comments: | ||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
7(A). |
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms. | ||||||
7.0.A | LIVING ROOM Fridge: Viking Comments: | ||||||
Living room | |||||||
| |||||||
7.1.A | CEILINGS - Comments: | ||||||
7.2.A | WALLS - Comments: | ||||||
7.3.A | FLOORS - Comments: | ||||||
7.4.A | OUTLETS AND WALL SWITCHES - Comments: | ||||||
7.5.A | DOORS (REPRESENTATIVE NUMBER) Interior Doors: Hollow core, French Comments: | ||||||
Rear exit door has loose and damaged weather strip. | |||||||
7.6.A | WINDOWS (REPRESENTATIVE NUMBER) Window Types: Single Pane Aluminum Sliders Comments: | ||||||
7.7.A | BEDROOM - Comments: | ||||||
Two bedrooms. Bedroom window frame has chain anchored for exterior light | |||||||
| |||||||
| |||||||
7.8.A | CEILING - Comments: | ||||||
7.9.A | WALLS - Comments: | ||||||
7.10.A | FLOOR - Comments: | ||||||
7.11.A | DOORS - Comments: | ||||||
7.12.A | OUTLETS AND WALL SWITCHES - Comments: | ||||||
7.13.A | KITCHEN - Comments: | ||||||
Kitchen | |||||||
| |||||||
7.14.A | CEILING - Comments: | ||||||
7.15.A | WALLS - Comments: | ||||||
7.16.A | WINDOWS - Comments: | ||||||
7.17.A | FLOOR - Comments: | ||||||
7.18.A | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS - Comments: | ||||||
Tap control unit is loose on sink in kitchen | |||||||
7.19.A | SHUT OFFS FOR TAPS - Comments: | ||||||
7.20.A | PLUMBING DRAIN, WASTE AND VENT SYSTEMS IN THIS UNIT - Comments: | ||||||
7.21.A | APPLIANCE SERIAL NUMBERS - Comments: | ||||||
Appliance serial numbers | |||||||
| |||||||
7.22.A | REFRIGERATOR - Comments: | ||||||
7.23.A | RANGES/OVENS/COOKTOPS Range/Oven: WHITE WESTINGHOUSE Comments: | ||||||
7.24.A | RANGE HOOD Exhaust/Range hood: VENTED, BROAN Comments: | ||||||
7.25.A | HEATING EQUIPMENT Heat Type: Hot Water Radiators Comments: | ||||||
Hot water radiators are heat source for apartment. | |||||||
7.26.A | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM - Comments: | ||||||
7.27.A | LOCATION OF MAIN AND DISTRIBUTION PANELS Panel capacity: 125 AMP Panel Type: Circuit breakers Comments: | ||||||
125 amp Cutler Hammer sub panel is on wall outside of kitchen area. | |||||||
| |||||||
7.28.A | OUTLETS AND WALL SWITCHES - Comments: | ||||||
Right side purple bedroom has loose outlet on front corner. | |||||||
7.29.A | SMOKE DETECTORS - Comments: | ||||||
7.30.A | STEPS, STAIRWAYS, BALCONIES AND RAILINGS - Comments: | ||||||
7.31.A | BATHROOM - Comments: | ||||||
7.32.A | SINK - Comments: | ||||||
Sink | |||||||
| |||||||
7.33.A | BATHTUB - Comments: | ||||||
Shower unit | |||||||
| |||||||
7.34.A | GFCI OUTLET - Comments: | ||||||
7.35.A | TOILET - Comments: | ||||||
7.36.A | CEILING - Comments: | ||||||
Damage to drywall over sink in apt #1 | |||||||
| |||||||
7.37.A | WALL - Comments: | ||||||
7.38.A | FLOOR - Comments: | ||||||
7.39.A | WINDOW - Comments: | ||||||
7.40.A | OTHER - Comments: | ||||||
Whirlpool washer and dryer serial numbers | |||||||
| |||||||
7.41.A | PORCHES OR DECKS - Comments: | ||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
7(B). |
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms. | ||||||
7.0.B | LIVING ROOM Fridge: GE Comments: | ||||||
Living and dining room have previous water damage at wall and ceiling joint. | |||||||
| |||||||
| |||||||
7.1.B | CEILINGS - Comments: | ||||||
| |||||||
| |||||||
7.2.B | WALLS - Comments: | ||||||
7.3.B | FLOORS - Comments: | ||||||
7.4.B | OUTLETS AND WALL SWITCHES - Comments: | ||||||
7.5.B | DOORS (REPRESENTATIVE NUMBER) Interior Doors: Hollow core Comments: | ||||||
7.6.B | WINDOWS (REPRESENTATIVE NUMBER) Window Types: Single pane, Single-hung, Thermal/Insulated Comments: | ||||||
7.7.B | BEDROOM - Comments: | ||||||
Bedroom | |||||||
| |||||||
7.8.B | CEILING - Comments: | ||||||
7.9.B | WALLS - Comments: | ||||||
7.10.B | FLOOR - Comments: | ||||||
7.11.B | DOORS - Comments: | ||||||
7.12.B | OUTLETS AND WALL SWITCHES - Comments: | ||||||
7.13.B | KITCHEN - Comments: | ||||||
Kitchen | |||||||
| |||||||
7.14.B | CEILING - Comments: | ||||||
7.15.B | WALLS - Comments: | ||||||
7.16.B | WINDOWS - Comments: | ||||||
7.17.B | FLOOR - Comments: | ||||||
7.18.B | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS - Comments: | ||||||
7.19.B | SHUT OFFS FOR TAPS - Comments: | ||||||
7.20.B | PLUMBING DRAIN, WASTE AND VENT SYSTEMS IN THIS UNIT - Comments: | ||||||
7.21.B | APPLIANCE SERIAL NUMBERS - Comments: | ||||||
Appliance serial numbers | |||||||
| |||||||
7.22.B | REFRIGERATOR - Comments: | ||||||
7.23.B | RANGES/OVENS/COOKTOPS Range/Oven: GENERAL ELECTRIC, GAS Comments: | ||||||
7.24.B | RANGE HOOD Exhaust/Range hood: VENTED, NUTONE Comments: | ||||||
7.25.B | HEATING EQUIPMENT Heat Type: Hot Water Radiators Comments: | ||||||
7.26.B | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM - Comments: | ||||||
7.27.B | LOCATION OF MAIN AND DISTRIBUTION PANELS Panel capacity: 100 AMP Panel Type: Fuses Comments: | ||||||
| |||||||
| |||||||
| |||||||
7.28.B | OUTLETS AND WALL SWITCHES - Comments: | ||||||
7.29.B | SMOKE DETECTORS - Comments: | ||||||
7.30.B | BATHROOM - Comments: | ||||||
7.31.B | SINK - Comments: | ||||||
Sink counter has some separating laminate at side rail | |||||||
| |||||||
7.32.B | BATHTUB - Comments: | ||||||
Bathtub | |||||||
| |||||||
7.33.B | GFCI OUTLET - Comments: | ||||||
7.34.B | TOILET - Comments: | ||||||
Toilet is loose and should be re-secured to prevent water leakage. | |||||||
7.35.B | CEILING - Comments: | ||||||
7.36.B | WALL - Comments: | ||||||
7.37.B | FLOOR - Comments: | ||||||
Hall floor drops at entrance to bathroom | |||||||
7.38.B | WINDOW - Comments: | ||||||
7.39.B | OTHER - Comments: | ||||||
| |||||||
| |||||||
7.40.B | PORCHES OR DECKS - Comments: | ||||||
| |||||||
| |||||||
| |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
7(C). |
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms. | ||||||
7.0.C | LIVING ROOM Fridge: GE Comments: | ||||||
Living and dining room | |||||||
| |||||||
7.1.C | CEILINGS - Comments: | ||||||
7.2.C | WALLS - Comments: | ||||||
7.3.C | FLOORS - Comments: | ||||||
Floors squeak through out apartment. Hard wood flooring | |||||||
7.4.C | OUTLETS AND WALL SWITCHES - Comments: | ||||||
7.5.C | DOORS (REPRESENTATIVE NUMBER) Interior Doors: Hollow core Comments: | ||||||
7.6.C | WINDOWS (REPRESENTATIVE NUMBER) Window Types: Single-hung, Thermal/Insulated Comments: | ||||||
7.7.C | BEDROOM - Comments: | ||||||
Bedroom and office. | |||||||
| |||||||
7.8.C | CEILING - Comments: | ||||||
7.9.C | WALLS - Comments: | ||||||
7.10.C | FLOOR - Comments: | ||||||
Bedroom has area of hardwood flooring that has been
replaced.
| |||||||
| |||||||
7.11.C | DOORS - Comments: | ||||||
Office door doesn't latch. Requires striker plate adjustment | |||||||
7.12.C | OUTLETS AND WALL SWITCHES - Comments: | ||||||
7.13.C | KITCHEN - Comments: | ||||||
Kitchen | |||||||
| |||||||
7.14.C | CEILING - Comments: | ||||||
7.15.C | WALLS - Comments: | ||||||
7.16.C | WINDOWS - Comments: | ||||||
7.17.C | FLOOR - Comments: | ||||||
7.18.C | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS - Comments: | ||||||
7.19.C | SHUT OFFS FOR TAPS - Comments: | ||||||
7.20.C | PLUMBING DRAIN, WASTE AND VENT SYSTEMS IN THIS UNIT - Comments: | ||||||
7.21.C | APPLIANCE SERIAL NUMBERS - Comments: | ||||||
Appliance serial numbers | |||||||
| |||||||
7.22.C | REFRIGERATOR - Comments: | ||||||
7.23.C | RANGES/OVENS/COOKTOPS Range/Oven: BEAUMARK Comments: | ||||||
7.24.C | RANGE HOOD Exhaust/Range hood: RE-CIRCULATE, NUTONE Comments: | ||||||
7.25.C | HEATING EQUIPMENT Heat Type: Hot Water Radiators Comments: | ||||||
7.26.C | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM - Comments: | ||||||
7.27.C | LOCATION OF MAIN AND DISTRIBUTION PANELS Panel capacity: 100 AMP Panel Type: Fuses Comments: | ||||||
Electrical panel is located in kitchen storage cupboard. Panel is Amalgamated 100 amp with copper wire. | |||||||
| |||||||
7.28.C | OUTLETS AND WALL SWITCHES - Comments: | ||||||
7.29.C | SMOKE DETECTORS - Comments: | ||||||
7.30.C | BATHROOM - Comments: | ||||||
7.31.C | SINK - Comments: | ||||||
Sink and toilet | |||||||
| |||||||
7.32.C | BATHTUB - Comments: | ||||||
Bathtub has cracked grout on shower wall. | |||||||
| |||||||
7.33.C | GFCI OUTLET - Comments: | ||||||
7.34.C | TOILET - Comments: | ||||||
7.35.C | CEILING - Comments: | ||||||
7.36.C | WALL - Comments: | ||||||
7.37.C | FLOOR - Comments: | ||||||
7.38.C | WINDOW - Comments: | ||||||
7.39.C | PORCHES OR DECKS - Comments: | ||||||
| |||||||
| |||||||
| |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
7(D). |
The building inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central to building; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of an installed heat source in each room. The building inspector shall describe: Energy source; and Heating equipment and distribution type. The building inspector shall operate the systems using normal operating controls. The building inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The building inspector is not required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues; Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms. | ||||||
7.0.D | LIVING ROOM Fridge: McClary Comments: | ||||||
Living and dining area | |||||||
| |||||||
7.1.D | CEILINGS - Comments: | ||||||
7.2.D | WALLS - Comments: | ||||||
7.3.D | FLOORS - Comments: | ||||||
7.4.D | OUTLETS AND WALL SWITCHES - Comments: | ||||||
Reversed polarity in dining room area | |||||||
7.5.D | DOORS (REPRESENTATIVE NUMBER) Interior Doors: Hollow core Comments: | ||||||
7.6.D | WINDOWS (REPRESENTATIVE NUMBER) Window Types: Single Pane Aluminum Sliders Comments: | ||||||
7.7.D | BEDROOM - Comments: | ||||||
Bedroom | |||||||
| |||||||
7.8.D | CEILING - Comments: | ||||||
7.9.D | WALLS - Comments: | ||||||
7.10.D | FLOOR - Comments: | ||||||
7.11.D | DOORS - Comments: | ||||||
7.12.D | OUTLETS AND WALL SWITCHES - Comments: | ||||||
7.13.D | KITCHEN - Comments: | ||||||
Kitchen | |||||||
| |||||||
7.14.D | CEILING - Comments: | ||||||
7.15.D | WALLS - Comments: | ||||||
7.16.D | WINDOWS - Comments: | ||||||
7.17.D | FLOOR - Comments: | ||||||
7.18.D | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS - Comments: | ||||||
7.19.D | SHUT OFFS FOR TAPS - Comments: | ||||||
7.20.D | PLUMBING DRAIN, WASTE AND VENT SYSTEMS IN THIS UNIT - Comments: | ||||||
7.21.D | APPLIANCE SERIAL NUMBERS - Comments: | ||||||
Appliance serial numbers | |||||||
| |||||||
| |||||||
7.22.D | REFRIGERATOR - Comments: | ||||||
7.23.D | RANGES/OVENS/COOKTOPS Range/Oven: GENERAL ELECTRIC, GAS Comments: | ||||||
7.24.D | RANGE HOOD Exhaust/Range hood: VENTED, NUTONE Comments: | ||||||
7.25.D | HEATING EQUIPMENT Heat Type: Hot Water Radiators Comments: | ||||||
7.26.D | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM - Comments: | ||||||
7.27.D | LOCATION OF MAIN AND DISTRIBUTION PANELS Panel capacity: 100 AMP Panel Type: Fuses Comments: | ||||||
Amalgamated 100 amp panel is located in bedroom closet. | |||||||
| |||||||
7.28.D | OUTLETS AND WALL SWITCHES - Comments: | ||||||
7.29.D | SMOKE DETECTORS - Comments: | ||||||
7.30.D | BATHROOM - Comments: | ||||||
7.31.D | SINK - Comments: | ||||||
Sink has reversed polarity at outlet. Recommend having repaired. Adding GFCI protection is recommended although not required. | |||||||
| |||||||
7.32.D | BATHTUB - Comments: | ||||||
Bathtub | |||||||
| |||||||
7.33.D | GFCI OUTLET - Comments: | ||||||
7.34.D | TOILET - Comments: | ||||||
7.35.D | CEILING - Comments: | ||||||
7.36.D | WALL - Comments: | ||||||
7.37.D | FLOOR - Comments: | ||||||
7.38.D | WINDOW - Comments: | ||||||
7.39.D | OTHER - Comments: | ||||||
7.40.D | PORCHES OR DECKS - Comments: | ||||||
Wood steps up to unit C porch on 3rd floor have the
following deficiencies:
| |||||||
| |||||||
| |||||||
| |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | |||
8. |
The building inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main over current device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages; The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior plumbing fixtures, and all receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and Smoke detectors. The building inspector shall describe: Service amperage and voltage; Service entry conductor materials; Service type as being overhead or underground; and Location of main and distribution panels. The building inspector shall report any observed aluminum branch circuit wiring. The building inspector shall report on presence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The building inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any over current device except ground fault circuit interrupters; Dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; Security system devices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or Built-in vacuum equipment. | |||||
8.0 | SERVICE ENTRANCE CONDUCTORS Electrical Service Conductors: Below ground Comments: | |||||
8.1 | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS Panel capacity: 400 AMP Panel Type: Circuit breakers Comments: | |||||
Grounding connections in front of hydro room are corroded and loose. Recommend replacement of clamps. | ||||||
| ||||||
8.2 | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE Branch wire 15 and 20 AMP: Copper Wiring Methods: Romex Comments: | |||||
8.3 | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) - Comments: | |||||
| ||||||
| ||||||
8.4 | POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE - Comments: | |||||
8.5 | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) - Comments: | |||||
8.6 | LOCATION OF MAIN AND DISTRIBUTION PANELS - Comments: | |||||
Main electrical shut off is located in basement hydro room | ||||||
8.7 | PANELS AND AMPERAGE - Comments: | |||||
8.8 | SMOKE DETECTORS - Comments: | |||||
| ||||||
8.9 | CARBON MONOXIDE DETECTORS - Comments: | |||||
8.10 | FIRE ALARM PANEL - Comments: | |||||
Notifier 500 fire alarm panel has cover removed. System was in trouble and indicated battery was dis-connected. | ||||||
| ||||||
8.11 | FIRE PULL STATIONS - Comments: | |||||
Fire alarm pull stations are located at all exits in apartments and restaurant. | ||||||
8.12 | EMERGENCY LIGHTING - Comments: | |||||
Emergency lighting tested and working. | ||||||
8.13 | EXIT LIGHTS - Comments: | |||||
Exit light at basement washroom area was not working at time of inspection. | ||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
9(A). | |||||||
9.0.A | CEILING CEILING: DRYWALL WALLS: PLYWOOD OVER BRICK FLOOR: CONCRETE DOORS: FIRE RATED Comments: | ||||||
Hydro room equipment list:
| |||||||
| |||||||
| |||||||
| |||||||
| |||||||
| |||||||
9.1.A | WALLS - Comments: | ||||||
| |||||||
| |||||||
| |||||||
9.2.A | FLOOR - Comments: | ||||||
9.3.A | DOORS - Comments: | ||||||
9.4.A | FIRE SEPARATION - Comments: | ||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
9(B). | |||||||
9.0.B | CEILING CEILING: DRYWALL WALLS: DRYWALL FLOOR: CONCRETE DOORS: FIRE RATED Comments: | ||||||
| |||||||
| |||||||
| |||||||
| |||||||
| |||||||
| |||||||
9.1.B | WALLS - Comments: | ||||||
9.2.B | FLOOR - Comments: | ||||||
9.3.B | DOORS - Comments: | ||||||
9.4.B | FIRE SEPARATION - Comments: | ||||||
| |||||||
| |||||||
| |||||||
9.5.B | COMBUSTION AIR - Comments: | ||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||
10. | |||||
10.0 | TYPE OF HEAT Heat Energy Source: Natural Gas Type of Heat Equipment: Hot Water Circulating Boiler, Natural Gas Furnaces Comments: | ||||
| |||||
10.1 | MANUFACTURER - Comments: | ||||
KeepRite | |||||
10.2 | DATE AND SERIAL NUMBER - Comments: | ||||
10.3 | CONDITION OF HEATING SYSTEM - Comments: | ||||
10.4 | LOCATION - Comments: | ||||
Furnaces are located in basement utility area. Boiler is located in boiler room at front of basement | |||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
11. | |||||||
11.0 | MANUFACTURER MAKE OF AIR CONDITIONER: KEEPRITE NUMBER OF UNITS: 2 Comments: | ||||||
Both units are KeepRite | |||||||
11.1 | BTU's - Comments: | ||||||
Both units are 4 ton capacity. 29.1 amp per unit | |||||||
11.2 | MODEL & SERIAL NUMBER - Comments: | ||||||
Unit #1 Model CAC048AKC4 Serial E053909606
Unit #2 Model CAC048AKC4 Serial E053909607
| |||||||
| |||||||
11.3 | LOCATION - Comments: | ||||||
Two central air conditioner units are located on rear of roof. | |||||||
| |||||||
11.4 | DEFICIENCIES - Comments: | ||||||
Insulation is missing from compressor line. Recommend adding insulation. | |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
12. | |||||||
12.0 | TYPE OF UNIT - Comments: | ||||||
| |||||||
| |||||||
12.1 | LOCATION OF UNIT - Comments: | ||||||
| |||||||
| |||||||
12.2 | CONDITION OF UNIT - Comments: | ||||||
Roof top exhaust unit has loose covers. Working condition is unknown. | |||||||
| |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
13. | |||||||
13.0 | HANDRAILS - Comments: | ||||||
Handrail is loose on front stairwell leading to apartments. | |||||||
13.1 | PULL STATIONS - Comments: | ||||||
13.2 | EMERGENCY LIGHTS - Comments: | ||||||
13.3 | ELECTRICAL - Comments: | ||||||
First floor outlet has reversed polarity and cord stapled to wall feeding door bells. | |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
14(A). | |||||||
14.0.A | CEILINGS CEILING: DRYWALL WALLS: DRYWALL, UNFINISHED FLOOR: VINYL TILES DOORS: HOLLOW WOOD Comments: | ||||||
Side office. Addon construction | |||||||
| |||||||
14.1.A | WALLS - Comments: | ||||||
Rear wall of office has exhaust fan which discharges into hallway. This is not permitted, discharge has to go outside. | |||||||
| |||||||
14.2.A | FLOOR - Comments: | ||||||
14.3.A | DOORS - Comments: | ||||||
14.4.A | WINDOWS - Comments: | ||||||
14.5.A | FIRE SEPARATION - Comments: | ||||||
14.6.A | LIFE SAFETY EQUIPMENT - Comments: | ||||||
14.7.A | ELECTRICAL DEFICIENCIES - Comments: | ||||||
| |||||||
| |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
14(B). | |||||||
14.0.B | CEILINGS CEILING: DRYWALL WALLS: DRYWALL FLOOR: CONCRETE Comments: | ||||||
Two KeepRite natural gas furnaces. 2005 models
| |||||||
| |||||||
| |||||||
| |||||||
14.1.B | WALLS - Comments: | ||||||
14.2.B | FLOOR - Comments: | ||||||
Condensate lines for furnaces are not draining into hole in floor. Hole in floor may not be trapped and could be source for sewer gas to enter building. | |||||||
| |||||||
14.3.B | DOORS - Comments: | ||||||
14.4.B | WINDOWS - Comments: | ||||||
14.5.B | FIRE SEPARATION - Comments: | ||||||
14.6.B | LIFE SAFETY EQUIPMENT - Comments: | ||||||
Rear exit door was padlocked and could not be inspected. | |||||||
14.7.B | ELECTRICAL DEFICIENCIES - Comments: | ||||||
| |||||||
| |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
14(C). | |||||||
14.0.C | CEILINGS CEILING: DRYWALL WALLS: DRYWALL FLOOR: CONCRETE DOORS: FIRE RATED Comments: | ||||||
Utility area | |||||||
| |||||||
14.1.C | WALLS - Comments: | ||||||
Sign on plumbing about previous flooding of basement. | |||||||
| |||||||
14.2.C | FLOOR - Comments: | ||||||
14.3.C | DOORS - Comments: | ||||||
14.4.C | WINDOWS - Comments: | ||||||
14.5.C | FIRE SEPARATION - Comments: | ||||||
| |||||||
| |||||||
| |||||||
| |||||||
14.6.C | LIFE SAFETY EQUIPMENT - Comments: | ||||||
14.7.C | ELECTRICAL DEFICIENCIES - Comments: | ||||||
| |||||||
| |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
14(D). | |||||||
14.0.D | CEILINGS CEILING: DRYWALL WALLS: DRYWALL & PANELING FLOOR: CONCRETE DOORS: MISSING Comments: | ||||||
| |||||||
| |||||||
| |||||||
| |||||||
14.1.D | WALLS - Comments: | ||||||
14.2.D | FLOOR - Comments: | ||||||
14.3.D | DOORS - Comments: | ||||||
14.4.D | WINDOWS - Comments: | ||||||
14.5.D | FIRE SEPARATION - Comments: | ||||||
14.6.D | LIFE SAFETY EQUIPMENT - Comments: | ||||||
14.7.D | ELECTRICAL DEFICIENCIES - Comments: | ||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | ||||
14(E). | |||||||
14.0.E | CEILINGS - Comments: | ||||||
| |||||||
| |||||||
| |||||||
| |||||||
14.1.E | WALLS - Comments: | ||||||
14.2.E | FLOOR - Comments: | ||||||
14.3.E | DOORS - Comments: | ||||||
14.4.E | WINDOWS - Comments: | ||||||
14.5.E | FIRE SEPARATION - Comments: | ||||||
14.6.E | LIFE SAFETY EQUIPMENT - Comments: | ||||||
14.7.E | ELECTRICAL DEFICIENCIES - Comments: | ||||||
Extension cord passes through cooler to 12 v transformer in ceiling. This is not permitted and permanent wiring should be installed. | |||||||
| |||||||
IN=Inspected | NI=Not Inspected | NP=Not Present | RR=Repair or Replace |
IN | NI | NP | RR | |||
14(F). | ||||||
14.0.F | CEILINGS CEILING: DRYWALL WALLS: DRYWALL FLOOR: CONCRETE DOORS: HOLLOW WOOD Comments: | |||||
14.1.F | WALLS - Comments: | |||||
14.2.F | FLOOR - Comments: | |||||
14.3.F | DOORS - Comments: | |||||
14.4.F | WINDOWS - Comments: | |||||
14.5.F | FIRE SEPARATION - Comments: | |||||
No fire separation in rear liquor storage room. Ceiling has been removed. | ||||||
| ||||||
14.6.F | LIFE SAFETY EQUIPMENT - Comments: | |||||
14.7.F | ELECTRICAL DEFICIENCIES - Comments: | |||||
Certified Building Code Official
7 Stollar Blvd
Barrie ON L4M 6N8
705-795-8255
Customer
Commercial Investor
Address
4567 Great Street to Be On
Investment City of Choice ON
1. Roofing, Roof Structure, Chimneys, and Attic | |||||||||||||||||||||||||||
|
2. Exterior | |||||||||||||||||||||||||||
|
5(B). Ladies Washroom | |||||||||
|
5(C). Staff Men's Room | |||||||||
|
6(A). Front Bar Area | |||||||||
|
6(B). Rear Bar Area | |||||||||
|
6(C). Kitchen Area | |||||||||
|
7(A). Unit #1 | |||||||||||||||||||||||||||
|
7(B). Unit #2 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
7(C). Unit #3 | |||||||||||||||||||||||||||||||||||||||||||||
|
9(B). Boiler Room | |||||||||
|
12. Exhaust Units | |||||||||
|
13. Stair Wells | |||||||||
|
14(C). Utility Area | |||||||||
|
14(D). Pot Washing Room | |||||||||
|
14(F). Liquor Storage Room | |||||||||
|
Certified Building Code Official
7 Stollar Blvd
Barrie ON L4M 6N8
705-795-8255
Customer
Commercial Investor
Address
4567 Great Street to Be On
Investment City of Choice ON
5(C). Staff Men's Room | |||||||||
|
6(A). Front Bar Area | |||||||||
|
7(A). Unit #1 | |||||||||
|
7(D). Unit #C | |||||||||
|
8. Electrical System for Building | ||||||||||||||||||||||||||||||||||||
|
9(A). Hydro Room | |||||||||
|
14(A). Side Office | |||||||||
|
14(B). Furnace Area | |||||||||
|
14(C). Utility Area | |||||||||
|
14(E). Walk-in Coolers | |||||||||
|
Certified Building Code Official
7 Stollar Blvd
Barrie ON L4M 6N8
705-795-8255
Customer
Commercial Investor
Address
4567 Great Street to Be On
Investment City of Choice ON
4. Plumbing System for Building | ||||||||||||||||||
|
5(D). Staff Ladies Room | |||||||||
|
7(A). Unit #1 | |||||||||
|
7(B). Unit #2 | |||||||||
|
9(B). Boiler Room | |||||||||
|
14(B). Furnace Area | |||||||||
|
14(C). Utility Area | |||||||||
|
Certified Building Code Official
7 Stollar Blvd
Barrie ON L4M 6N8
705-795-8255
Customer
Commercial Investor
Address
4567 Great Street to Be On
Investment City of Choice ON
7(D). Unit #C | |||||||||
|
Certified Building Code Official
7 Stollar Blvd
Barrie ON L4M 6N8
705-795-8255
Customer
Commercial Investor
Address
4567 Great Street to Be On
Investment City of Choice ON
9(B). Boiler Room | |||||||||
|
11. Air Conditioners | |||||||||
|
14(A). Side Office | |||||||||
|
14(B). Furnace Area | |||||||||
|
INVOICE |
Napoleon Home Inspections
Certified Building Code Official 7 Stollar Blvd Barrie ON L4M 6N8 705-795-8255 Inspected By: Roger Frost - Certified Building Code Official |
Inspection Date: 2020-02-20
Report ID: 1001001111110 |
Customer Info: | Inspection Property: |
Commercial Investor
Customer's Real Estate Professional: |
4567 Great Street to Be On Investment City of Choice ON |
| ||||||||
Tax $117.00 | ||||||||
Total Price $1017.00 |
Payment Method: Invoiced
Payment Status: Invoice Included with Report
Note: Mail cheque to Roger Frost, 7 Stollar Blvd, Barrie, ON L4M 6N8
This inspection was performed in accordance with and under the terms of a Pre-Inspection Agreement. The agreement was signed and agreed upon prior to the preparation of this report and a signed copy of the agreement is available upon request. An unsigned copy of the agreement may be attached to this report for your information or it may also be available on the company web site.
If you were happy with your inspection and would like to add a comment or like on Facebook it would be greatly appreciated. Facebook Link
Thank you,
Roger Frost